34 51 68   85 102 136 170 204 238
A 830 930 1050 1150 1250 1500 1700 1850 2050
B 480 580 700 800 900 1150 1350 1500 1700
Weight Kg 22.5 26.5 28 32 34 50 56 60 65

Fp-vc vertical concealed fan coil unit

model

size

34 51 68 85 102 136 170 204 238
A 590 690 810 910 1010 1260 1460 1610 1810
B 480 580 700 800 900 1150 1350 1500 1700
Weight Kg 20 21.2 22.5 23.7 24.8 23.1 28.4 30.1 31.7

 

Fan coil

Overview

The FP series fan-coil air conditioner is mainly composed of a fan, a motor, a heat exchanger (coil), a condensate tray, a shell, and a controller. It is suitable for centralized air-conditioning systems. Due to the low noise and flexible temperature adjustment characteristics of the fan coil produced by our company, it is widely used in hotels, guesthouses, apartments, restaurants, hospitals, commercial office buildings, and other places.

 

Model meaning and description

Note:

  1. High static pressure unit refers to the static pressure at the outlet of the horizontal concealed unit which is 30Pa or 50Pa;
  2. Measurement of cooling capacity under nominal conditions: indoor dry bulb temperature 27C, wet bulb temperature 19.5°C;
  3. Heat measurement under nominal conditions: the indoor dry bulb temperature is 21℃, and the water supply is the same as the flow under nominal conditions;
  4. Water resistance refers to the water resistance at the rated flow;
  5. The input power refers to the input power at high-end air volume.

 

For example FC51-HC -R

Water inlet method code

Left style: L

Right style: R

Model code:

Horizontal concealed installation: HC

Horizontal opening installation: HO

Vertical concealed installation: VC

Vertical opening installation: VO

Wall-mounted: WM

Column type: CT

Nominal air volume: 10 times the specification figure

Product code: Indicates fan coil

Note:

The distinction between left and right styles: When looking at the air outlet of the fan coil, the left-hand side of the piping is the left style, and vice versa when it is the right style.

 

The core advantage of the product

  1. Beautiful appearance and corrosion resistance: The galvanized sheet produced by Baogang, is free of spangles, and the surface is not easy to be oxidized and has strong corrosion resistance. No welds, the overall appearance is beautiful and generous. The slope of the water pan is designed to be non-condensing. The water pan is formed by a one-time integral stamping process, with a sloped water outlet, and both sides of the steel plate are pickled and phosphate, and then electrostatically sprayed to prevent water leakage. The surface is covered with flame-retardant insulation material to completely prevent condensation on the surface.
  2. High heat exchange efficiency: the coil adopts seamless red copper tube string aluminum fin structure, the aluminum sheet adopts louver open skylight type slotted fin, the copper tube diameter is 9.52, and high-quality hydrophilic aluminum foil is selected. The tube is expanded hydraulically or mechanically to ensure that the aluminum sheet is tightly combined with the copper tube, and the heat exchange efficiency is increased by 10%. The unit test pressure is 1.6Mpa to ensure no leakage.
  3. Ultra-low noise: The core component of the coil adopts a hot-dip galvanized multi-blade centrifugal fan that conforms to the principle of aerodynamics. After strict dynamic and static balance testing, the unit runs smoothly and the noise is lower than the national standard.
  4. 80,000 hours of operation without failure: the motor adopts a 110 type 24-slot copper core motor, the motor bearing adopts moisture-proof sealing treatment, no need to replenish lubricating oil, equipped with overheating protection device, low-temperature rise, no special circumstances, stable operation of the motor without failure.
  5. The DC variable frequency fan coil adopts a DC brushless motor, and its noise is close to perfect when running at low speed, and the operating power is 1/3 of the ordinary fan coil. Random configuration brand thermostat, intelligent control, and monitoring of indoor temperature and humidity.

 

Main parameters of fan coil air conditioner

Model comparison British model FC200 FC300 FC400 FC500 FC600 FC800 FC1000 FC1200 FC1400
standard modle FP-3.5 FP-5.0 FC- 6.3

7.1

FP-8 FP-10 FP-12.5

14

FP-16 FP-20 PF-25
Gb model FP-34 FP-51 FP-65 FP-85 FP-102 FP-136 FP-170 FP-204 FP-238
Air volume

M3/H

High 340 510 680 850 1020 1360 1700 2040 2380
Middle 255 383 510 638 765 1020 1275 1530 1785
low 170 255 340 425 510 680 850 1020 1190
Cooling capacity

W

High 1800 2700 3600 4500 5400 7200 9000 10800 12800
Middle 1620 2440 3290 4120 4850 6550 8190 9730 11580
low 1310 2010 2650 3320 3900 5300 6610 7860 9350
Heat supply

W

High 2700 4050 5400 6750 8100 10800 13500 16200 18900
Middle 2350 3520 4530 6040 6850 9260 11750 14140 16360
low 1620 2470 3130 4170 4740 6500 8180 9710 11290
Cold water supply temperature 7℃-12℃
Hot water supply temperature 60℃
power supply AC110-220V/50HZ
heat exchanger type Copper tube string aluminum sheet, sheet pitch 2.2mm
Three-row water supply KG/H 324 482 655 814 936 1276 1602 1915 2178
Water resistance KPa 30 30 30 30 40 40 40 40 50
Operating pressure 1.6MPa
Low static pressure unit input input power W 37 52 62 76 96 134 152 189 228
Motor Power W 8 12 18 22 32 20×2 25×2 35×2 42×2
High static pressure

unit static

Static pressure 30Pa input power W 44 59 72 87 108 156 174 212 253
Motor Power W 40 18 22 30 40 25×2 35×2 42×2 60×2
Static pressure 50Pa input power W 49 66 84 100 118 174 210 250 300
Motor Power W 16 22 30 40 50 35×2 42×2 60×2 75×2
Number of fans 1 2 2 2 2 3 4 4 4
Noise dB(A) Low static pressure unit ≤37 ≤39 ≤41 ≤43 ≤45 ≤46 ≤48 ≤50 ≤52
High static pressure 30Pa ≤40 ≤42 ≤44 ≤46 ≤47 ≤48 ≤50 ≤52 ≤54
High static pressure 50Pa ≤42 ≤44 ≤46 ≤47 ≤49 ≤50 ≤52 ≤54 ≤56