Forward-leaning centrifugal fan (centrifugal induced draft fan)
Forward-leaning centrifugal fan usually adopts type A direct connection and type C belt drive two structural forms. With an explosion-proof motor and impeller made of aluminum (or stainless steel), it can be made into an explosion-proof centrifuge. Forward-leaning multi-wing centrifugal impeller, with large air volume, low noise, compact structure, and other advantages.
Product use:
Application: Widely used in large and medium-sized factories and civil buildings, large squares, power plants, air treatment equipment, hot air circulation equipment supporting.
Requirements for conveying gas: non-flammable, explosive, non-corrosive gas medium.
Restrictions on air dust: no sticky substance is allowed in the gas, and the content of dust and hard particles is not more than 150mg/m3. If it is used to transport small particle materials, the service life of the impeller of the fan will be shortened.
Normal temperature: the normal operating temperature of the fan is not more than 80° C. If there is any special problem, please contact the technical department of our company.
For example:
Model: D315 (Type A is directly connected, type C pulley)
Material: carbon steel, stainless steel (optional)
Speed: 1420 r/min
Air Volume: 3500-5200 m3 / h
The total pressure: 750-830 pa
Motor power: 2.2KW
1 detail design: the fan is designed according to the three-way flow theory, with a flat forward impeller. Aerodynamics single blade arc blade.
2 General performance: choose the configuration of frequency conversion motor, achieve performance transformation, achieve the parameters of the stepless adjustment, to meet the different needs of customers on the product.
3 Wide applicability:
A: Theaters, hotels, office buildings, and other places
B: Supporting products of all kinds of central air-conditioning units, HVAC, purification, and ventilation equipment.
factory inspection: all products are tested and tested before leaving the factory.
Product parameters
Technical performance parameters of kXFD forward-leaning centrifugal heart fan (type A direct connection)
Model | (r/min) speed | (m3/h) Air volume | (Pa) Full pression | Motor model | Work (KW) |
200 | 1400 | 750-1600 | 310-240 | 71M-4 | 0.37 |
2840 | 1300-2300 | 1250-1150 | 90L-2 | 2.2 | |
225 | 1390 | 1200-220 | 410-350 | 80M-4 | 0.55 |
2880 | 2000-3200 | 1610-1570 | 100L-2 | 3 | |
250 | 1390 | 2000-3000 | 510-450 | 80M-4 | 0.75 |
2900 | 4160-6235 | 2205-1945 | 132S-2 | 5.5 | |
280 | 1400 | 2500-3800 | 660-600 | 90L-4 | 1.5 |
2930 | 5050-7680 | 2695-2450 | 160M-2 | 15 | |
315 | 1420 | 3500-5200 | 830-750 | 100L-4 | 2.2 |
355 | 940 | 4000-6000 | 460-390 | 100L-6 | 1.5 |
1440 | 5000-8000 | 1050-950 | 112M-4 | 4 | |
400 | 960 | 5300-7500 | 600-550 | 132S-6 | 3 |
1440 | 7000-11000 | 1330-1100 | 132S-4 | 5.5 | |
450 | 960 | 7000-11200 | 750-650 | 132M-6 | 4 |
500 | 960 | 10000-14200 | 880-800 | 132M-6 | 5.5 |
560 | 970 | 14000-18500 | 1180-1100 | 160M-6 | 7.5 |
630 | 720 | 10000-15500 | 850-800 | 160L-8 | 5.5 |
970 | 16000-23000 | 1480-1300 | 160L-6 | 11 | |
710 | 730 | 16650-26640 | 1007-910 | 200L-8 | 15 |
We will contact you within 1 working day.