Ceiling type air conditioning unit

Product details

Ceiling type air conditioning unit

Ceiling type air conditioning unit is a kind of combined air treatment, just adjust the way of installation, its combined principle is unchanged.  It’s own without cold and heat source, with hot and cold water or steam as the medium, to complete the air filtration, purification, heating, cooling, humidification, dehumidification, clear sound, fresh air processing, and other functions.

Fresh air into the air conditioning unit and indoor to return air mixture in the mixing section, after coarse efficiency filter air mixture, removal of dust and debris, and then after effect tachycardia in the period of the secondary filter, filter the smaller dust and debris, and then, through the cold or heat section in the table after cooling or heating air is made to reach the required temperature,  Then through the humidification section to the humidity required by the system, that is, to reach the specified air supply state point, and finally through the fan section to send the processed air into the room.

Ceiling air conditioning function segment: Generally only initial and medium effect segment, surface cooling segment, heating segment, humidification segment, fan segment, etc.  (The basic structure is the third paragraph) Example: BFP-40 (ultra-thin)

Pressure: 160-200 pa

Cold capacity: 22.4 to 59.3 kW

Heat: 38.1 to 65.3 kw

Water volume: 3.9-10.2 (T/h)

Water resistance: 9.1 to 19.8 kpa

Power: 0.32 * 2 kw

Noise: 58 dB

Weight: 166-185kg (for reference only)

 

01 Detail Design

Adopt frame and plate structure, no cold bridge design, water pan integral stamping molding.  Internal oxidation treatment, the whole water pan stamping molding.

 

02 Process performance

Beautiful appearance design, product process continuous improvement, improve quality acceptance standards.

 

03 Wide applicability

A: Theaters, high-end hotels, high-end office buildings, and other places.

B: Supporting products of all kinds of central air-conditioning units, HVAC, purification, and ventilation equipment.

 

04 Delivery Inspection

All products are tested before leaving the factory.

 

BFP variable air volume air conditioning unit technical and energy reference table

performance

model

Air Volume (m3/h) Residual Pressure(Pa) Cold capacity(KW) Heat capacity(KW) Water volume(T/h) Water resistance(Kpa) Power:(KW) Noise dB(A) weight(Kg)
Return air condition Fresh air condition Return air condition Fresh air condition Return air condition Fresh air condition Return air condition Fresh air condition
BFP-20W/L 2000 200 11.2 22.5 19.1 28.00 1.9 3.9 3.5 4.2 0.32 55 140/160
BFP-20XW/L 160 13.9 29.7 25.7 32.67 2.4 5.1 4.5 5.6 160/190
BFP-30W/L 3000 260 16.8 33.8 28.6 42.00 2.9 5.8 4.5 6.4 0.55 56 160/180
BFP-30XW/L 220 20.8 44.5 38.5 49.00 3.6 7.7 5.3 8.5 180/210
BFP-40W/L 4000 320 22.4 45.1 38.1 56.0 3.9 7.7 4.6 6.7 0.75 58 195/220
BFP-40XW/L 280 27.7 59.3 51.3 64.33 4.8 10.2 6.5 12.4 225/255
BFP-45W/L 4500 340 25.2 50.7 42.9 63.00 4.3 8.7 5.2 8.6 0.75 58 205/220
BFP-45XW/L 300 31.2 66.8 57.8 73.50 5.1 11.5 7.4 15.4 215/235
BFP-50W/L 5000 400 28.0 56.3 47.7 70.00 4.8 9.7 6.8 10.7 1.1 59 220/235
BFP-50XW/L 360 34.7 74.2 64.2 81.67 6.0 12.8 8.1 19.5 230/255
BFP-55W/L 5500 450 30.8 62.0 52.4 77.00 5.3 10.7 6.5 12.7 1.5 59 238/256
BFP-55XW/L 400 38.1 81.6 70.6 89.83 6.6 14.0 9.5 20.3 256/286
BFP-60W/L 6000 450 33.6 67.6 57.2 84.00 5.8 11.6 7.4 14.8 1.5 60 258/285
BFP-60XW/L 400 41.6 89.0 77.0 98;0 7.2 15.3 11.3 28.2 285/312
BFP-70W/L 7000 500 39.2 78.9 66.7 98.00 6.7 13.6 8.5 16.5 1.8 61 282/312
BFP-70XW/L 460 48.5 103.8 89.8 114.33 8.3 17.9 14.6 33.3 315/346
BFP-80W/L 8000 600 44.8 90.1 76.3 112.00 7.7 15.5 9.6 18.4 2.2 62 310/345
BFP-80XW/L 560 55.5 118.7 102.7 130.67 9.5 20.4 16.4 39.6 338/369
BFP-90W/L 9000 600 50.4 101.4 85.8 126.00 8.7 17.4 10.6 22.4 2.2 63 322/358
BFP-90XW/L 560 62.4 133.5 115.5 147.00 10.7 23.0 18.2 43.6 345/369
BFP-100W/L 10000 600 56.0 112.7 95.3 140.00 9.6 19.4 12.4 26.7 3.0 64 336/368
BFP-100XW/L 560 69.3 148.3 128.3 163.33 11.9 25.5 21.6 48.6 356/389
BFP-120W/L 12000 600 67.2 135.2 114.4 168.00 11.6 23.2 18.7 40.1 1.8*2 64 438/475
BFP-120XW/L 560 83.2 178.0 154.0 196.00 14.3 30.6 28.4 53.2 476/506
BFP-150W/L 15000 600 84.0 169 143.0 210.00 12.4 29.1 22.6 42.6 2.2*2 64 520/550
BFP-150XW/L 560 104.0 222.5 192.5 245.00 17.9 38.3 35.7 73.5 562/598
BFP-180W/L 18000 600 100.8 202.8 171.6 252.00 17.3 34.9 25.1 44.2 3.0*2 65 556/581
BFP-180XW/L 560 124.8 267.0 231.0 294.00 21.5 45.9 47.7 78.2 585/615
BFP-200W/L 20000 600 112.0 225.3 190.7 280.00 19.3 38.7 28.7 46.5 3.0*3 65 576/595
BFP-200XW/L 560 138.7 296.7 256.7 326.67 23.8 51.6 82.6 610/638
BFP-230W/L 23000 650 128.8 259.1 219.3 322.00 22.1 44.6 29.7 48.7 4.0*2 68 612/635
BFP-230XW/L 600 159.5 342.1 295.2 375.67 27.4 58.7 51.6 85.2 639/672
BFP-250W/L 25000 650 140.0 281.7 238.3 350.00 24.1 48.4 26.5 49.6 4.0*2 69 652/686
BFP-250XW/L 600 173.3 370.8 320.8 408.33 29.8 63.8 50.2 82.6 710/732
BFP-280W/L 28000 650 156.8 315.5 266.9 392.00 27.0 54.2 32.6 43.6 5.5*2 70 679/712
BFP-280XW/L 600 194.1 415.3 359.3 457.33 33.4 71.4 54.5 92.5 729/758
BFP-300W/L 30000 650 168.0 338.0 286.0 420.00 28.9 58.1 36.9 52.3 5.5*2 70 712/735
BFP-300XW/L 600 208.0 445.0 385.0 490.00 35.8 76.5 57.2 91.2 765/796
BFP-350W/L 35000 650 196.0 394.3 333.7 490.00 33.7 67.8 38.7 59.4 7.5*2 72 826/998
BFP-350XW/L 600 242.7 519.2 449.2 571.67 41.7 89.3 58.7 96.2 910/1110

Note: 1. Return air condition: air drying bulb temperature 27℃, wet bulb temperature 19.5℃, water inlet temperature 7℃, water inlet temperature 5℃.

Air drying bulb temperature for heating 15℃ hot water inlet temperature 60℃

2, fresh air condition: cooling inlet air-drying bulb temperature 34℃, wet bulb temperature 28℃, water inlet temperature 7C, inlet water temperature difference 5℃.  Air drying bulb temperature of heating -4℃, hot water inlet temperature of 60℃.